PLC WECON LX1V Series / LX1V-1208MR-D (Relay output) / IO: 12xDI/8xDO , Interface Port : 1 x RS485 PLC LX1V ราคาประหยัด
หมวดหมู่ : FACTORY AUTOMATION ,  PLC & Modules ,  CPU , 
แบรนด์ : WECON
Share
Technical information | |
Running mode | Cycle scan / Interrupt |
Programming | Instruction list / Ladder |
Total instructions | Basic Instructions: 27 / Applied Instruction: 138 |
Execute time | Basic Instructions: 0.06us / Applied Instruction: 1~10us |
System Storage | 16Kbyte |
Download/ Monitoring | Programming Cable USB Type C |
External Interrupt | 6 Channels |
Timer Interrupt | 3 Channels |
High Speed input single | 2 Channels 200KHz , 4 Channels 5KHz |
High Speed input AB | 1 Channels 100KHz support 2 or 4 frequency multiplication |
1 Channels 5KHz support 2 or 4 frequency multiplication | |
Filter | For all X input terminals |
Electrical data | |
Supply voltage | DC type 24VDC ±10% |
Power consumption | DC type ≤30W |
Power Outage Time | 1ms |
Power Fuse | 250V 3.15A |
DC type <15A 1ms / DC 24V | |
Power Output | <8W |
Backup battery | YES |
Outputs | |
Digital input Power Supply | DC 24V |
Output Mode | Relay |
Output function | dry contact |
Output Circuit | AC 250VAC ; DC 30VDC |
Common output current | N/A |
Insulation | Mechanistic |
Leak current | N/A |
Min. Load | N/A |
Max.Load | Resistive ; 2A point 8A COM port |
Inductive ; 80VA | |
General ; 100W | |
Response Time | <10ms |
High Speed Pulse Output | N/A |
Operating environment | |
Ambient temperature [°C] | 0..55 |
Storage temperature [°C] | -20..70 |
Ambient humidity [%RH] | 35..85 |
Protection | IP20 |
Tests / approvals | |
Shock Resistance | JIS C 0040 Standard |
Influence Immunity | Meet the IEC61000-4-4 and GB/T 17626.4 standard |
Noise voltage amplitude 1KVP-P | |
pulse width 10us, period 0.3 s, edge time 5ns, duration 1min. | |
Vibration resistance | 10…50Hz (1.5mm) |
Approval | CE , FCC , ISO9001 |
Mechanical data | |
Housing material | ABS |
Mounting | DIN-Rail |
Dimensions [mm] | 114 x 107.2 x 50.5 |
Connection I/O | Terminal |
Software / Interface | |
Software | Wecon PLC Editor1 |
Interface port | COM1 RS485 |
Protocol | WECON protocol / Modbus RTU |
_______________________________________________________________________________________________
LX1V DATASHEET Download
____________________________________________________________________________________________________